kW
(kVA) Ratings
|
|
Model
Number LPWG2
|
7.0
Natural Gas
|
8.5
HD-5 Propane
|
|
Standby
|
Prime
|
Standby
|
Prime
|
|
1
PH 60 Hz, 1.0 PF
|
14.4(14.4)
|
13.1
(13.1)
|
18.0
(18.0)
|
16.4
(16.4)
|
|
3
PH 60 Hz, 0.8 PF
|
15.0
(18.7)
|
13.6
(17.0)
|
18.7
(23.4)
|
17.0
(21.2)
|
|
1
PH 50 Hz, 1.0 PF
|
11.7
(11.7)
|
10.6
(10.6)
|
14.6
(14.6)
|
13.3
(13.3)
|
|
3
PH 50 Hz, 0.8 PF
|
11.6
(14.5)
|
10.5
(13.1)
|
14.5
(18.1)
|
13.2
(16.5)
|
|
Engine
Statistics @ 60Hz Rated Load
|
|
Engine
Model LPWG2
|
Natural
Gas
|
HD-5
Propane
|
|
Number
of Cylinders
|
4
|
|
Cylinder
Displacement
|
113.5
cu in
1.8 liter
|
|
Mean
Piston Speed
|
945
ft/min
4.8 m/sec
|
|
Exhaust
Gas Flow
|
97.5
(79.7) cfm
66.3 (55.2) l/sec
|
113.5
(92.2) cfm
53.6 (43.8) l/sec
|
|
Exhaust
Temperature
|
1000°
F
540° C
|
1100°
F
595° C
|
|
Max.
Back Pressure
|
15"
water
37 mbar
|
|
Governor
Droop
|
0%
|
|
Steady
State Freq. Regulation
|
±0.25%
|
|
Combustion
Air
|
46.6
(39.4) cfm
22.0 (18.6) l/sec
|
48.6
(40.9) cfm
22.9 (19.3) l/sec
|
|
Cooling
Air Flow
|
2500
(2000) cfm
1.18 (0.94) m³/sec
|
|
Fuel
Consumption
|
|
Load
|
Cu
Ft/Hr
Cu Meter/Hr
|
Cu
Ft/Hr
Cu Meter/Hr
|
|
100%
|
205.7
(156.5)
5.8 (4.4)
|
86.7
(67.3)
2.5 (1.9)
|
|
75%
|
171.4
(133.3)
4.8 (3.8)
|
75.0
(58.1)
2.1 (1.6)
|
|
50%
|
134.6
(105.9)
3.8 (3.0)
|
57.6
(45.3)
1.6 (1.3)
|
|
Generator
Statistics @ Rated Load
|
|
Generator
Manufacturer
|
Newage
|
|
Voltage
Change with
100% Load Step Applied
|
within
3% (1/4 sec)
|
|
Telephone
Influence Factor (TIF)
|
Less
than 50
|
|
Voltage
Regulation
|
2%
all loads to 100%
|
|
Total
Harmonic Factor (THF)
|
Less
than 2%
|
|
Temperature
Rise
|
125°
C
|